Electric Power:
Cat EGP Switchgear
Contact Us About This Product
Click a link to download the document:
- Configuration
- Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
- Modes of Operation
- Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
- Application
- LV and MV (208V - 38 kV)
- Operating Temperature
- 0°C to 50°C
EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source.
Product Specs
-
Technical Summary
- Configuration
- Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
- Modes of Operation
- Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
- Application
- LV and MV (208V - 38 kV)
- Configuration
- Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
- Modes of Operation
- Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
- Application
- LV and MV (208V - 38 kV)
-
Environmental Parameters
- Operating Temperature
- 0°C to 50°C
- Storage Temperature
- -20°C to +60°C
- Medium Voltage Standards
- NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
- Certifications
- IBC, CBC, UBC & OSHPD Certified
- Control Panel Enclosure
- NEMA 1 or NEMA 3R Freestanding Construction
- Low Voltage Standards
- NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
- Operating Temperature
- 0°C to 50°C
- Storage Temperature
- -20°C to +60°C
- Medium Voltage Standards
- NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
-
Generator Protective Devices
- ANSI Protective Devices
- 15/25, 27/59, 81 O/U, 32, 40, 50, 51
Equipment
-
- Egp Switchgear
-
- Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
- Emergency Stop Button for each generator
- Instant Auto Switch
- Generator Demand Priority Control
- Audible Alarm & Horn Silence Button
- Circuit Breaker Control Switch with Indicators
-
- Data Table Interface
-
- * Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
-
- Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
-
- * Provides additional discrete synchronization protection
-
- Remote Power Monitoring System
-
- * To monitor breaker status, alarms, metering and other operating parameters