Diesel Generator Sets:
3512C Generator Set
Contact Us About This Product
Click a link to download the document:
- Height - Maximum
- 110 in
- Length - Maximum
- 262.9 in
- Duty Cycle
- Standby, Mission Critical
- Width - Maximum
- 89.8 in
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Product Specs
-
Generator Set Dimensions
- Height - Maximum
- 110in
- Length - Maximum
- 262.9in
- Width - Maximum
- 89.8in
- Dry Weight - Genset (maximum)
- 32660lb
-
Generator Set Specifications
- Duty Cycle
- Standby, Mission Critical
- Width - Minimum
- 89.8
- Minimum Rating
- 1750 ekW
- Maximum Rating
- 1750 ekW
- Voltage
- 380 to 13800 Volts
- Frequency
- 60 Hz
- Speed
- 1800 rpm
- Emissions/Fuel Strategy
- U.S. EPA Cert., Tier 2
-
Engine Specifications
- Fuel System
- 8.46in
- Engine Model
- 3512C ATAAC, V-12, 4-Stroke Water-Cooled Diesel
- Compression Ratio
- 14.7:1
- Aspiration
- TA
- Governor Type
- Adem™3
- Fuel System
- Electronic unit injection
- Bore
- 6.69in
- Displacement
- 3574in³
- Stroke
- 8.46in
Equipment
-
- Air Inlet System
-
- Air cleaner; single element canister type with service indicator
-
- Cooling
-
- Package mounted radiator
-
- Exhaust
-
- Exhaust flange outlet
-
- Fuel
-
- Primary fuel filter with integral water separator
- Fuel priming pump
- Secondary fuel filter
-
- Generator
-
- Matched to the performance and output characteristics of Cat engines
- IP23 Protection
-
- Power Termination
-
- Busbar
-
- Control Panel
-
- EMCP 4 Genset Controller
-
- Control System
-
- Generator set packages include Caterpillar' s Voltage Regulator (IVR). IVR includes reactive droop capability, 3-phase voltage sensing, KVAR / PF modes, RFI suppression, min/max exciter. Limiter and exciter diode monitor
- Emergency stop pushbutton
- Oil pressure (psi, kPa or bar)
- 1 Programmable digital outputs
- Accessory module data link
- 4 Programmable relay outputs (Form A)
- kVAr-hr (total)
- Reverse power (kW) (32)
- kVAr (per phase, average & percent)
- Amps (per phase & average)
- Over / under frequency (81 o/u)
- EMCP 4.2B
- PLC functionality
- 1 Programmable relay outputs (Form C)
- Programmable protective relaying functions:
- RPM
- Frequency (Hz)
- Low coolant level
- Number of I/O varies on options selected
- Lamp test
- kVA (per phase, average & percent)
- Emergency stop
- kW (per phase, average & percent)
- Engine cool-down timer
- Speed adjust
- Generator phase sequence
- Over / under voltage (27/59)
- Warning/shutdown with common LED indication of shutdowns for:
- Customer data link (Modbus RTU)
- Volts (L-L & L-N)
- High coolant temperature
- Engine cycle crank
- True RMS AC metering, 3-phase, +/-2% accuracy
- Low coolant temperature
- Low oil pressure
- Cat Connect
- Digital indication for:
- Communications
- Environmental sealed front face
- Reverse reactive power (kVAr) (32RV)
- 24 Volt DC operation
- Power Factor (per phase & average)
- Overspeed
- Auto / start / stop control
- Load histogram feature
- Controls:
- Failure to start (overcrank)
- Customizable screens
- kW-hr (total)
- Text alarm / event descriptions
- Alarm acknowledge
- Overcurrent (50/51)
- Generator mounted - rear facing
- Coolant temperature
- DC volts
-
- Governing System
-
- ADEM III
-
- Cooling System
-
- SCAC
- Fan and belt guards
- Caterpillar extended life coolant (Not included with packages without radiator, installed SF44CTS
- Coolant level sensors (Not included with packages without radiator)
- Radiator fan and fan drive
- Coolant drain line with valve
-
- Exhaust System
-
- Flanged faced outlet(s)
- Dry exhaust manifold
-
- Fuel System
-
- Secondary fuel filters
- Fuel priming pump
- Fuel cooler; not included with packages without radiator
- Flexible fuel lines - shipped loose
-
- Generators And Attachments
-
- Random wound
- Permanent magnet
- High voltage
- Six lead
- NEMA standard hole pattern
- NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime / 150C standby)
- NEMA Class H insulation, Class H temperature rise at 40C ambient (125C prime/150C standby)
- Class H insulation, Class F temperature rise at 40C ambient (105C prime/130C standby)
- NEMA standard hole pattern
- Winding temperature detectors
- NEMA standard hole pattern
- Internal excitation
- Form wound
- 3 Phase brushless, salient pole
- Bus bar connections, right side extension box, bottom cable entry
- Low voltage:
- Busbar connections, top center mounted, top cable entry
- Medium voltage:
-
- Literature
-
- English
-
- Lube System
-
- Oil drain lines and valve
- Lubricating oil
- Oil filter, filler and dipstick
- Fumes disposal
- Gear type lube oil pump
- Integral lube oil cooler
-
- Mounting System
-
- Rubber anti-vibration mounts (shipped loose)
-
- Starting / Charging System
-
- Battery and battery rack w/cables
- 45 Amp charging alternator
- 24 Volt electric starting motor
- Battery disconnect switch
-
- General
-
- Paint - Caterpillar Yellow except rails and radiators gloss black
- SAE Standard Rotation
- Right hand servicing
- Flywheel and Flywheel housing-SAE No. 00
- Paint: Caterpillar yellow with high gloss black rails & radiator
-
- Control Panels
-
- Digital I/O module
- EMCP 4.3, EMCP 4.4
- Load share module
- Remote monitoring software
- Generator temperature monitoring & protection
-
- Exhaust
-
- Exhaust mufflers
-
- Air Inlet System
-
- Heavy duty air cleaner
- Single element filter
-
- Generator
-
- Permanent magnet excitation (PMG)
- Anti-condensation heater
- Internal excitation (IE)
- Oversize and premium generators
-
- Power Termination
-
- Circuit breakers, IEC compliant
- Circuit breakers, UL listed
-
- Cooling System
-
- Standard installed radiators
- Standard installed ATAAC radiators
- Optional installed ATAAC radiators
- Water level switch gauges
- Coolant
- Optional installed radiators
-
- Exhaust System
-
- Flanges
- Flange and exhaust expanders
- Flexible fittings
- Elbows
- Y Adapters
- Mufflers
-
- Fuel System
-
- Primary fuel filter
-
- Starting/charging
-
- Heavy-duty starting system
- Charging alternator
- Battery chargers
- Oversize batteries
- Air starting motor with control and silencer
- Jacket water heater
-
- Generators And Attachments
-
- 1400, 1600, 2700 Frames
- Space heater
- Generator conversion from IE to PM
- Differential current transformers (DCT) 15 kV class
- RW, IE, 6 leads, Pitch 0.6667
- Generator air cleaner
- Low Voltage: 380,440 / 480 Volts, 3 Phase, 1800 rpm
- Differential current transformers (DCT) 8.7 kV class
-
- Instrumentation
-
- Wiring GP W/O cyl sensors
- Pyrometer and thermocouples
-
- Lube System
-
- Oil drains
- Lubrication oil in standard sump
- Oil level regulator
- Prelube pumps
-
- General
-
- US aid emblem
- The following options are based on regional and product configuration:
- Automatic transfer switches (ATS)
- EU Certificate of Conformance (CE)
- CSA Certification
- Integral & sub-base UL listed dual wall fuel tanks
- EEC Declaration of Conformity
- UL 2200 package
- Integral & sub-base fuel tanks
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Enclosures: sound attenuated, weather protective
-
- Crankcase Protection
-
- Crankcase ventilation system
- No explosion relief valves
- No crankcase explosion relief valve
- Explosion relief valve
-
- Mounting System
-
- Spring type vibration isolators
- IBC vibration isolators
- Puck style low efficiency isolators
-
- Mounting
-
- IBC isolators
- Rubber anti-vibration mounts
- Spring-type vibration isolator
-
- Power Connections
-
- 1600 ,2000, 2500, 3000, 4000 Amp, 3 Pole, UL-100% rated circuit breakers
- Grounding groups
- Neutral ground connections
- Right side power connections
- Rear power connections
- Left side power connections
- Six lead, six terminal option
- 2000, 2500,3200 Amp, 3 Pole, IEC Rated Circuit Breakers
- Center post busbar
- 2000, 2500 Amp, 4 Pole, IEC Rated Circuit Breakers
- Cable entry - Right side
-
- Special Tests / Reports
-
- Fuel consumption test
- Generator test report
- IBC seismic certification
- PGS test report @ 1.0 power factor
- Standard engine test charge
- CSA certification
- Generator fuel consumption test
- Torsional vibration analysis
- PGS test report @ 0.8 power factor
-
- Starting / Charging System
-
- 24 Volt battery set - Dry
- Air pressure regulator
- 10 Amp battery charger
- Air starting motor
- 35 Amp battery charger
- Jacket water heaters
- Starter covers
- Engine barring device
- Batteries, racks and cables:
- Electric starting motors