Skip to content
Logo

Overview

1250 ekW Generator Set for Standby applications

Key Features

More Comfort. More Performance. More Versatility.

Accepts 100% Block Load

Demonstrated capability to pick up large on-site loads

Full Power up to 50°C Ambient

Provides full power even on hottest days of the year

Conforms to ISO8528-5 G3 Load Acceptance

Maintains voltage and frequency during transient events

Specifications

Maximum Rating 1250 ekW
Minimum Rating 1250 ekW
Emissions/Fuel Strategy U.S. EPA Tier 2
Voltage 380 - 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby
Engine Model C32 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 5.71 in
Stroke 6.38 in
Displacement 1958.86 in³
Compression Ratio 15.0:1
Aspiration TA
Fuel System EUI
Governor Type Ademâ„¢A4
Length - Minimum 164.3 in
Length - Maximum 164.3 in
Width - Minimum 82.3 in
Width - Maximum 82.3 in
Height - Minimum 89.3 in
Height - Maximum 89.3 in
Dry Weight - Genset (minimum) 15776 lb
Dry Weight - Genset (maximum) 15776 lb

Our Locations