Overview

Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a compact package. A Bypass Isolation Automatic Transfer Switch (ATS) provides fully functioning transfer in applications where emergency power to critical loads must be maintained at all times with no interruption. This type of design allows for inspection, maintenance or replacement of the power switching mechanisms with no interruption in electrical service. Breaker based Bypass isolation ATS are available from 200A to 5,000A.

Key Features

More Comfort. More Performance. More Versatility.

ATC-900 microprocessor-based controller and Power Breaker

Full 30-cycle short time withstand capability
30-cycle, 85 kA short-time rating on power circuit breaker

All controls relays and industrial grade relays

Lugs are 90� rated and all control wire is #16 AWG, type XLPE with a 125� temperature rating.

Durable Durable powder-coated steel NEMA 1, 3R or 12 enclosures with three door hinges.

The hinges have removable hinge pins to facilitate door removal and are supplied with pad-lockable latches.

Specifications

Rating Range200-5000A
Transfer TypeBypass isolation, Closed transition
Switch TypePower Breaker
Control Power200-5000A, 2-, 3-, 4-pole<br>100% rated Short
System Voltage Application120-600 Vac 50/60 Hz
Time Withstand85,000 for 30 cycles
Withstand100 kAIC at 600V, 3 cycles
Applicable TestingCSA C22.2 No. 178 certified<br> UL 1008 listed up to 3200A<br>4000A, and 5000A UL 891 listed